High-density AI
Luleå Aurora
- Facility
- 60 MW
- IT load
- 50 MW
- Target PUE
- 1.20
32,768 H200 GPUs
4,096 eight-GPU servers; approximately 41 MW including hosts. Remaining IT allowance covers fabric and storage.
80–120 kW / AI rack
- Power sourcing
- Swedish grid connection with a proposed hydro-backed PPA; firm capacity remains grid-dependent.
- Cooling
- Warm-water liquid loop with dry coolers; winter economization.
- Heat reuse
- Proposed 10 MWth export to Luleå district heating via heat pumps. Seasonal demand and utility acceptance govern delivery.
Full EPC · 130 kV substation · direct-to-chip cooling
Scenario: phased build; SE1 grid capacity and heat offtake subject to agreement.